OdoNash Specifications

 

TECHNICAL SPECIFICATIONS

ODONASH ODOR REMOVAL SYSTEM

        1. 1. Material of construction of all parts shall be Stainless Steel.
        2. 2. Shall comprise individual compartments for Ozone Generator, Fan, Electrical / Instrumentation Components., and Sewer Vent Air Extraction Fan.
        3. 3. Ozone Generator Compartment shall comprise set of multi plate, double sided corona discharge plates operating at high voltage, to produce adequate quantity of ozone at medium concentration.
        4. 4. The system shall not require any replacement consumable except air filter, and maintenance shall be minimum subject to timely replacement of intake air filter to the unit.
        5. 5. Feed air shall be plant room air. Use of annular tube type corona with compressed air as feed gas is not permissible, so as to prevent deposition of nitrogen oxides on the corona surface. To minimize maintenance cost, labor and time, and operational consumable, use of oxygen feed system is not permissible.
        6. 6. The ozone generating corona and ozone wetted parts shall be confined in a fully welded stainless steel enclosure to prevent ozone leaks. It shall be provided with openable glass or plexi glass panel for inspection of corona plates while the equipment is in operation. The outer enclosure of the equipment shall be provided with lockable doors to provide easy access to the glass inspection panel.
        7. 7. The corona chamber shall not have any trace of exhaust air while it starts and operates. Necessary ROHS compliant and UL listed electrical relay shall be provided to ensure this safety feature.
        8. 8. The electrical compartment shall be isolated from all other compartments, and rated to NEMA 4X (IP 66).
        9. 9. The transformer shall be electrical induction type, UL listed. It shall not damage, burn, or elevate in temperature even if short circuit occurs. Shall revert to normal operation upon removal of short circuit. The transformer shall be fully encapsulated and housed in metallic enclosure for safety against moisture and water impregnation.
        10. 10. Passage of high voltage conductors across metallic enclosure shall be through UL listed liquid tight connectors.
        11. 11. High voltage cable shall be silicon insulated, ozone and corona resistant, rated for 20 KV, and UL listed with UL flame test rating.
        12. 12. Following accessories shall be provided in the electrical compartment;
          1. UL listed Manual Regulator to modulate production of ozone.
          2. UL listed Hour Meter housed in NEMA 4 enclosure for timely maintenance.
          3. Air Pressure Manometer for measurement of air pressure in fan chamber.
          4. UL listed switches such as DPST Main On/Off Switch, Fan On/Off Switch, Indicating Lamps, and Terminal Block.
        13. 13. Fan chamber shall comprise backward curved non overloading fan driven by thermal protected, UL listed TEFC motor to inject ozonized air into exhaust air stream. External static pressure of the fan shall be rated for injection into airstreams from 0.25" WG (60 Pa) up to 2" WG (500 Pa). Air intake shall be through grille with filter track and UL listed MERV 11 filter.
        14. 14. Sewage Vent Air Fan shall be of non-sparking, polypropylene material. Shaft shall be of Stainless Steel. The Motor shall be TEFC and UL listed. The Motor shall be outside the vent air stream.
        15. 15. Following materials may be field provided or factory provided as specified;
          1. Duct from sewer wells to vent air fan, material PVC or Stainless Steel
          2. Vent air discharge duct from fan to contact chamber, material PVC or Stainless Steel
          3. Interconnect duct from ozone generating equipment  to discharge duct from vent air fan, material PVC or Stainless Steel
          4. Contact Chamber to provide adequate contact time, material Stainless Steel or PVC
        16. 16. As Optional Item, Control Panel for automatic control of the system shall be provided if specified. This shall comprise;
          1. Control Panel fabricated to NEMA 4X
          2. H2S Monitor Model CZ10 or as specified
          3. DLC Controller Model CZ6-CX for automatic modulation of ozone production
          4. Residual Ozone Monitor Model CZ12 listed to UL 867A
        17. 17. The Equipment shall be of North American manufacture, with parts and components from USA and Canada.

 

 

*** Downloadable Brochure and Specifications are available in the Resources section of our website

Company News

Engineering Upgrade Announced

NuClimate Air Quality Systems, Inc is pleased to announce that it will be releasing new versions of its QLS (24" x 48") and Q1/Q1L (24" x 24") 1-way blow Chilled Beam unit during the 1st quarter of 2011.  This engineering upgrade will allow contractors to easily select left and right hand configurations to meet installtion demands.

Release of 2-Way Blow Induction Beam

NuClimate Air Quality Systems, Inc is pleased to announce that it will be releasing a 2-way blow Induction Beam unit during the 1st quarter of 2011. The unit will be available in two sizes 24" x 24" and 48" x 24". It will feature a fully functional drainpan in case latent conditioning is necessary. The unit will be available in 2 and 4 pipe configurations.

NuClimate announces Partnership with Carrier

June 1, 2012 NuClimate Air Quality Systems, Inc. is please to announce a new exclusive partnership with Carrier Air Conditioning for the OEM supply of its Chilled/Induction Beam line. Carrier's expertise and engineering tools will take this product to the next level! Stay tuned for more and check out our representative map for new representatives around the US and abroad.

Follow NuClimate on Facebook, Twitter & Linked-In

Follow NuClimate now on facebook and twitter and Linked-In!

http://twitter.com/NuClimate

http://www.facebook.com/NuClimateAirQualitySystems?ref=hl#!/NuClimateAirQualitySystems

http://www.linkedin.com/company/nuclimate-air-quality-systems-inc-?trk=nav_account_sub_nav_company_admin